Microgrid

DataCenterMicrogridEnv is a self-contained behind-the-meter microgrid that combines:

  • a DataCenter core (IT workload + cooling + thermal dynamics, see Resources),
  • battery storage with explicit feasibility,
  • exogenous PV generation (real or synthetic diurnal profile),
  • a dispatchable diesel generator with explicit fuel cost.

The microgrid runs grid-connected by default with a capped grid-import port (grid_import_p_max_mw, set to 1.5 MW in the canonical benchmark task config). Pure islanded operation corresponds to grid_import_p_max_mw = 0.0. Under simulated outages the microgrid switches to islanded mode, so any unmet load enters the power_deficit cost channel as a hard violation. Power balance is explicit and testable; the agent jointly decides GPU scheduling, cooling, storage, diesel, and (implicitly) the residual served by capped grid import.

This env drives the DC Microgrid benchmark task (benchmarks/dc-microgrid).

Why a separate env

DataCenterEnv models only the load. Attaching PV / battery / diesel as bundles to a TransGridEnv would not capture the islanded power-balance constraint or the multi-objective trade-off (energy vs cost vs carbon vs SLA). The composite env keeps the same JAX + RL implementation rules while exposing those objectives directly.

More concretely, this env is not "several full environments glued together". It is a composition layer with one DataCenterEnv sub-env for load and thermal dynamics, plus resource bundles for battery / PV / diesel, wrapped by a top-level microgrid step that enforces power balance and computes the final reward / cost outputs.

Architecture

flowchart TD
    DC["DataCenterEnv core<br/>IT + cooling + tasks"]
    PV["RenewableBundle (PV)<br/>profile-driven generation"]
    BT["BatteryBundle<br/>SOC dynamics + feasibility"]
    DG["DieselBundle<br/>fuel cost + carbon"]
    BAL["power balance<br/>residual = p_pv + p_dg + p_batt - p_load"]
    REW["scalar reward<br/>r_energy + w_cost*r_cost + w_carbon*r_carbon"]
    COST["costs = (cost_sla,<br/>cost_overtemp,<br/>cost_power_deficit)"]

    DC --> BAL
    PV --> BAL
    BT --> BAL
    DG --> BAL
    BAL --> REW
    BAL --> COST

Internally, DataCenterMicrogridEnv calls a private helper _dc_step_inner(...) that runs the inner DataCenter physics without its auto-reset, then applies a single unified auto-reset across all sub-states. This avoids double-resetting inside lax.scan.

State and parameters

classDiagram
    class DCMicrogridState {
        +dc (DataCenterState)
        +resource_states (tuple)
        +last_action
        +done
    }
    class DCMicrogridParams {
        +dc (DataCenterParams)
        +resources (tuple)
        +battery_deg_cost_per_mwh
        +w_cost  w_carbon
        +cpu_profile  outdoor_temp_profile
    }

The actual runtime schema is nested: the top-level env stores the DataCenterState plus one bundle state per attached resource. Convenience accessors such as state.soc, state.p_dg_mw, params.battery_power_mw, and params.solar_profile still exist for backward compatibility, but they are projections from the nested bundle structure rather than primary stored fields.

DieselParams is a small frozen helper struct: p_dg_max_mw, fuel_cost_per_mwh, emission_factor (in kgCO2 per kWh).

The optional profile fields cpu_profile and outdoor_temp_profile are JAX arrays of shape (T,). Profiles are indexed cyclically as arr[t % T]. PV lives on the attached RenewableBundle; when these profiles are absent, synthetic diurnal helpers from dc_microgrid_profiles.py are used.

Action

5-D Box:

Index Name Range Meaning
0 train_sched_rate [0, 1] fraction of GPU headroom to training
1 ft_sched_rate [0, 1] fraction of remaining headroom to finetuning
2 cooling_setpoint_norm [0, 1] maps to [t_set_min, t_set_max]
3 battery_power_norm [-1, 1] positive = discharge, negative = charge
4 dg_power_norm [0, 1] DG output as fraction of p_dg_max_mw

The first two entries are easy to misread. They are not fixed GPU counts or a one-shot split of the full cluster:

  • inference demand means the exogenous GPUs already occupied by online inference load in the current step.
  • urgent tasks are waiting jobs whose latest feasible start time has already arrived or passed, so they must be launched immediately to have any chance of meeting their deadline.
  • GPU headroom means the GPUs still available after subtracting inference demand and already-running urgent work.
  • train_sched_rate is applied first. It sets the training scheduler's GPU budget as a fraction of the current headroom.
  • ft_sched_rate is applied second, after the training scheduler has already consumed part of that headroom. It sets the finetuning budget as a fraction of the remaining headroom, not the original total.

In code terms, if the current step has gpus_avail = 600 and train_sched_rate = 0.5, then training receives a budget of 300 GPUs. If training actually uses 240, the env recomputes the residual headroom and ft_sched_rate is then applied to that smaller remainder.

The other three entries are direct physical controls:

  • cooling_setpoint_norm = 0 maps near t_set_min (colder, safer, but usually higher cooling power), while 1 maps near t_set_max (warmer, cheaper, but higher over-temperature risk).
  • battery_power_norm is first mapped to a desired MW dispatch, then clipped by both converter rating and SOC feasibility. The realised battery power can therefore be smaller in magnitude than the commanded value.
  • dg_power_norm maps to diesel output as a fraction of p_dg_max_mw. If a minimum-loading rule is enabled, very small positive commands can be interpreted as "off" or lifted to the minimum stable output.

Observation (24-D)

[cpu_util, mem_util, q_train_fill, q_ft_fill, queue_urgency,
 zone_temp_norm, outdoor_temp_norm, cop_ratio,
 solar_cf, soc, dg_margin_norm, p_load_norm, net_load_norm,
 batt_dis_headroom_norm, batt_chg_headroom_norm,
 grid_price_norm, grid_price_6h_max_norm,
 last_action_norm (5), sin(t), cos(t)]

The layout is frozen so policies trained on one profile pool remain forward-compatible with later pools.

The observation is interface-first rather than formula-first: the code field names stay visible so readers can map them back to the implementation. When a field is normalized, that normalization rule is part of its meaning:

  • solar_cf: current PV capacity factor
  • soc: current battery SOC
  • dg_margin_norm: remaining diesel margin, normalized by diesel capacity
  • p_load_norm: current DC load, normalized by total on-site supply capacity
  • net_load_norm: current net load after PV, normalized by dispatchable capacity
  • batt_dis_headroom_norm: currently feasible battery discharge power, normalized by converter rating
  • batt_chg_headroom_norm: currently feasible battery charge power, normalized by converter rating
  • grid_price_norm: current GB MID grid-import price, normalized by grid_price_ref_per_mwh (default 150.0)
  • grid_price_6h_max_norm: maximum grid-import price expected over the next six hours, same normalization, giving the policy a forward-looking arbitrage signal
  • last_action_norm (5): previous step's action vector, already in normalized control coordinates
  • sin(t), cos(t): periodic time-of-day features

Power balance and battery feasibility

Battery action is clipped by both converter rating and SOC headroom (same one-way efficiency rule as BatteryEnv):

\[ P_{\max}^{\text{dis}} = \min\!\left(P_{\text{rated}},\ \frac{(\mathrm{SOC} - \mathrm{SOC}_{\min})\, E_{\max}\, \eta_d}{\Delta t}\right) \]
\[ P_{\max}^{\text{chg}} = \min\!\left(P_{\text{rated}},\ \frac{(\mathrm{SOC}_{\max} - \mathrm{SOC})\, E_{\max}}{\eta_c\, \Delta t}\right) \]

Diesel and PV outputs are deterministic functions of the agent action and the exogenous profile. Power balance:

\[ \text{residual} = P_{\text{pv}} + P_{\text{dg}} + P_{\text{batt}} - P_{\text{load}} \]
\[ P_{\text{deficit}} = \max(-\text{residual}, 0),\quad P_{\text{spill}} = \max(\text{residual}, 0) \]

In plain terms: if PV + battery + diesel cannot cover the data-center load, the shortfall becomes \(P_{\text{deficit}}\), the unmet load power, and enters the cost channel. If supply is larger than load, the excess becomes \(P_{\text{spill}}\), the unused surplus power, and is reported in info only.

Scalar reward

\[ r_t = r_{\text{energy}} + w_{\text{cost}}\, r_{\text{cost}} + w_{\text{carbon}}\, r_{\text{carbon}} \]

with

\[ r_{\text{energy}} = -P_{\text{dc}}\, \Delta t \quad [\mathrm{MWh}] \]
\[ r_{\text{cost}} = -(C_{\text{fuel}} + C_{\text{deg}}) \]
\[ r_{\text{carbon}} = -\text{carbon\_kg} \]

where \(C_{\text{fuel}}\) is the diesel fuel cost for this step, and \(C_{\text{deg}} = |P_{\text{batt}}|\, \Delta t\, c_{\text{deg}}\) is the battery degradation cost with \(c_{\text{deg}} = \texttt{deg\_cost\_per\_MWh}\) in the implementation.

step() returns the scalar reward \(r_t\) above. Separately, info["reward_vector"] = [r_energy, r_cost, r_carbon] exposes the three unscaled reward components for analysis or for multi-objective RL methods that want the decomposed signal.

Constraint costs (CMDP channel)

\[ \text{costs} = (C^{\mathrm{sla}}_t, C^{\mathrm{temp}}_t, C^{\mathrm{deficit}}_t) \]

The static names are ("sla", "overtemp", "power_deficit"), mapping to \(\texttt{cost\_sla}\), \(\texttt{cost\_overtemp}\), and \(\texttt{cost\_power\_deficit}\) in the implementation. info["cost_sum"] is the sum of the reported cost components. These three subscripts (sla, temp, deficit) are the canonical short-forms used in the paper Appendix E.5 and in benchmarks/dc-microgrid.md.

Cost channel definitions:

Symbol Constraint name Info key Meaning
\(C^{\mathrm{sla}}_t\) sla cost_sla SLA violation density from the DataCenter task queue: expired jobs divided by n_gpus.
\(C^{\mathrm{temp}}_t\) overtemp cost_overtemp Normalized excess of zone temperature above the critical threshold.
\(C^{\mathrm{deficit}}_t\) power_deficit cost_power_deficit Unserved electrical load \(P_{\mathrm{def}} / \max(P_{\mathrm{load}}, \epsilon)\).

Time scale

The microgrid env defaults to delta_t_hours = 5/60 and max_steps = 288, giving a 24-hour episode at 5-minute resolution. This is finer than the 30-minute grid envs because both thermal dynamics and battery feasibility require a sub-15-minute step to be physically meaningful.

Real vs synthetic profiles

make_dcmicrogrid_params(...) builds a synthetic-only param object, suitable for tests. For real workload data:

from powerzoojax.envs.microgrid.dc_microgrid import (
    make_dcmicrogrid_params_with_profiles,
)
params = make_dcmicrogrid_params_with_profiles(source="google", n_steps=288)

For benchmark evaluation, the same env can be tested under both in-distribution and shifted conditions. To produce OOD eval splits, transform an existing params with apply_ood_transform(params, scenario) from powerzoojax.data.dc_microgrid_profiles. Valid scenarios: workload_swap, workload_shock, renewable_drought, cooling_stress, dg_derating, sla_tighten. The benchmark task uses cooling_stress and renewable_drought as OOD splits.

Cross references